EN 50268-2/EN45545-2 cable smoke density


EN 50268-2/EN45545-2 cable smoke density--Standard

EN 50268-2:2002 Common test methods for cables under fire conditions-Measurement of smoke density of cables burning under defined conditions-Part 2: Procedure.

EN 61034-2: Measurement of smoke density of cables burning under defined conditions---Part 2: Test procedure and requirement. EN 61034-2:2005 is identical with IEC 61034-2:2005.It supersedes EN 50268-2:2002 which is withdrawn.

Smoke density test is the combustion of an important aspect of performance evaluation, as it relates to the degree of difficulty for personnel evacuation.


EN 50268-2/EN45545-2 cable smoke density--Test method

Cable requirements straight, before testing the temperature 23 ¡æ ¡À 5 ¡æ placed under 16 hours in advance.

Experimental test time is 40 minutes, smoke density test by the lowest rate of light transmission


EN 50268-2/EN45545-2 cable smoke density¡ªScope
The European standard EN45545-2 R14 (interior for cable testing), R15 (exterior for cable testing) reference EN50268-2 electric wire & cable smoke density test.

According to the level of risk of running vehicles, EN45545-2 standard on the numerical density of smoke wire and cable are different.


EN 50268-2/EN45545-2 other standard
EN 50268-1:2002 Common test methods for cables under fire conditions-Measurement of smoke density of cables burning under defined conditions-Part 1: Apparatus.

DIN EN 50266-2-4: wire and cable bundles of multiple vertical flame (cable diameter ¡Ý 12mm), the need for this test cables and wires (not including cable), burning the maximum damage after the test cable length of less than 2.5 m.

DIN EN 50305 section 9.1.1: wire and cable bundles of multiple vertical flame (6mm <cable diameter <12mm) the need for this test cables and wires (not including cable), combustion test cable length does not exceed the maximum damage 2.5m.

DIN EN 50305 section 9.1.2: wire and cable bundles of multiple vertical flame (diameter ¡Ü 6mm cable required for this test cables and wires (not including cable), burning the maximum damage after the test cable length of no more than 2.5m.

DIN EN 60332-1-2: a single vertical wire and cable flame, the need for this test cables and wires, including the data line (fiber optic cables, data bus wire, coaxial cable), combustion tests, the cable length of the top damage not more than 50mm, the bottom does not exceed 540mm.